Results of the use of a new design thermometer for measuring the transient temperature of superheated steam in the boiler

Wyniki zastosowania termometru o nowej konstrukcji do pomiaru nieustalonej temperatury pary przegrzanej pary w kotle
Magdalena Jaremkiewicz, Dawid Taler

    Streszczenie
    The aim of the paper is to verify the effectiveness of the new technique of measuring the superheated steam
    temperature in the transient state in a power plant. It based on the application of a new design thermometer with calculation
    method using the solution of the inverse heat conduction problem. Steam temperature was also measured with an existing
    conventional thermometer so that the advantages of the new measurement technique could be assessed. Temperature
    measurements using both thermometers were made at the boiler start-up, boiler shut-off and during boiler operation. The
    thermometers were located downstream of the second superheater attemperator. The results of measurements were
    compared. The fastest change in steam temperature occurred after the sudden injection of water into the attemperator header.
    In this case, the temperature measurement errors with the conventional thermometer are the highest. Dynamic errors of
    steam temperature measurement using conventional thermometers exceeded 80 K. The measurements made show a much
    greater accuracy of the measurement of the transient steam temperature using the proposed new technique.